Category: Uncategorized

  • Standard sizes for the various round electrical panel knockouts

    Electrical panel knockouts and their corresponding hole sizes for drilling come in several standard sizes:

    1. 1/2″ trade size: 7/8″ (22.5mm) hole2
    2. 3/4″ trade size: 1-1/8″ (28.3mm) hole2
    3. 1″ trade size: 1-3/8″ (34.6mm) hole2
    4. 1-1/4″ trade size: 1-3/4″ (43.2mm) hole2
    5. 1-1/2″ trade size: 2″ (49.6mm) hole2
    6. 2″ trade size: 2-1/2″ (61.5mm) hole2
    7. 2-1/2″ trade size: 3″ (74mm) hole2
    8. 3″ trade size: 3-5/8″ (89.9mm) hole2
    9. 3-1/2″ trade size: 4-1/8″ (102.7mm) hole2
    10. 4″ trade size: 4-1/2″ (115.4mm) hole2

    When drilling these holes, you can use either a hole saw or a conduit knockout punch of the corresponding size2. For example, for a 1/2″ trade size conduit, you would use a 7/8″ hole saw or a 1/2″ conduit knockout punch2.

    It’s important to note that the trade size does not directly correspond to the actual hole size. The hole size is typically larger to accommodate the fittings and connectors used with the conduit.


    The difference between ‘trade size’ and actual size in electrical conduit is sigThe difference between ‘trade size’ and ‘hole size’ in electrical conduit and knockouts is significant:

    1. Trade size: This is a standardized label used in the electrical industry to identify conduit sizes. It does not directly correspond to the actual physical measurements of the conduit or knockout3.
    2. Hole size: This refers to the actual diameter of the hole that needs to be drilled or punched for the conduit to fit properly1.

    For example:

    • A 1/2″ trade size conduit requires a 7/8″ (22.5mm) hole1.
    • A 1″ trade size conduit needs a 1-3/8″ (34.6mm) hole1.

    The trade size system was developed to simplify conduit selection and ensure compatibility between components. However, it can be confusing for those unfamiliar with industry standards3.

    Understanding this distinction is crucial for electricians and DIY enthusiasts when selecting the appropriate conduit size and drilling the correct hole size for their specific installation needs. The hole size is typically larger than the trade size to accommodate the fittings and connectors used with the conduit14.


    the hole sizes mentioned for electrical conduit also apply to knockouts needed for connectors and other fittings12. These standardized sizes ensure compatibility between conduits, connectors, and electrical boxes. For example:

    1. A 1/2″ trade size conduit or connector requires a 7/8″ (22.5mm) knockout or hole.
    2. A 1″ trade size conduit or connector needs a 1-3/8″ (34.6mm) knockout or hole.
    3. A 1-1/4″ trade size conduit or connector fits into a 1-3/4″ (43.2mm) knockout or hole.

    This standardization allows electricians to use the same knockout sizes for both conduits and their corresponding connectors, simplifying installation and ensuring proper fit. When working with electrical panels or boxes, the knockout sizes are designed to accommodate these standard trade sizes for conduits and connectors34.

  • Furnace large custom duct collars for large ductboard return

    According to North Carolina building codes, there are specific requirements for constructing duct collars when building a large ductboard supply duct into the furnace:

    1. All connections, including the duct collar, must be sealed with water-based duct mastic1. This is critical for meeting the new North Carolina Energy Conservation Code (NCECC) requirements.
    2. Tape can be used during installation, but should not be relied upon as the primary method of air sealing ductwork1. Mastic should be applied over the tape to ensure airtightness.
    3. The duct collar should be properly sized and well-sealed where it meets the air handler1. This is particularly important due to the large size of plenums, as poor connections at the air handler can lead to significant leaks.
    4. When connecting the ductboard to metal components like the furnace, a metal collar or sleeve should be used to ensure a secure and airtight connection4.
    5. The duct collar must be constructed to meet the pressure class requirements of the system4. Each size in a pressure class has minimum specifications for joints and reinforcements.
    6. Proper support for the duct collar and adjacent ductwork is required. Metal straps with a minimum width of 1 inch (25 mm) and equivalent to or heavier gauge than the duct material should be used for support8.
    7. The duct collar should be designed to allow for proper airflow and minimize pressure drop in the system4.

    Remember to consult the specific North Carolina Mechanical Code and SMACNA guidelines for detailed requirements and best practices when constructing duct collars and connections.

  • Red Devil 0841DX F-Seal 181 Fiber Reinforced Water Based Duct Sealant -It is better than regular water based mastic

    Red Devil 0841DX F-Seal 181 Fiber Reinforced Water Based Duct Sealant is indeed considered a duct mastic and offers several advantages over regular water-based mastic:

    1. Fiber reinforcement: F-Seal 181 contains fibers that enhance its sealing strength and workability, making it more durable and effective for sealing duct joints12.
    2. UL listings: It is UL 181A-M and B-M listed, indicating it meets strict standards for use with both rigid fiberglass ductwork and flexible air ducts14.
    3. Versatility: F-Seal 181 is suitable for various HVAC applications, including metal ductwork, fiberglass duct board, and flex duct, both indoors and outdoors24.
    4. Performance: It exceeds all SMACNA pressure and sealing classes, providing excellent adhesion and flexibility14.
    5. Additional benefits: F-Seal 181 offers mold and mildew resistance, low VOC content, and contributes to LEED EQ Credit 4.124.

    While regular water-based mastic can be effective, F-Seal 181’s fiber reinforcement and specific formulation for HVAC applications make it a superior choice for many duct sealing tasks. Its fast drying time, excellent adhesion, and ability to seal high, medium, and low-pressure HVAC duct systems further set it apart from standard mastics45

    Red Devil 0841DX F-Seal 181 Fiber Reinforced Water Based Duct Sealant offers several environmental benefits:

    1. Low VOC content: The product has low volatile organic compound emissions, which contributes to better indoor air quality68.
    2. LEED compliance: It is LEED EQ 4.1 compliant, supporting green building practices and sustainability initiatives8.
    3. Water-based formula: Being water-based, it reduces the use of harmful solvents and is more environmentally friendly compared to solvent-based alternatives6.
    4. Improved energy efficiency: By effectively sealing HVAC duct systems, it helps reduce energy waste and improves overall system efficiency6.
    5. Durability: The fiber-reinforced formula provides long-lasting performance, reducing the need for frequent reapplication and minimizing waste6.
    6. Versatility: It can be used on various duct materials, including metal, fiberglass duct board, and flex duct, both indoors and outdoors, reducing the need for multiple specialized products68.
    7. Mold and mildew resistance: This feature helps maintain a healthier indoor environment and extends the life of the ductwork1.

    These environmental benefits align with Red Devil’s commitment to meeting product demands while helping to preserve the environment and complying with environmental health and safety regulations1.

  • IF Mastic is used to seal an hvac joint, do you still need to tape and mastic the tape?

    If mastic is used to seal an HVAC joint properly, there is generally no need to apply tape and then mastic over the tape. Mastic alone is considered sufficient for sealing duct joints when applied correctly12. Here’s why:

    1. Mastic is more durable and long-lasting than tape, often lasting up to 20 years or longer3.
    2. It creates a flexible, airtight seal that can withstand temperature changes and vibrations1.
    3. For small gaps (less than 1/4 inch), mastic can be applied directly to the joint without additional reinforcement4.

    However, there are some situations where using both tape and mastic might be beneficial:

    1. For medium gaps (1/4-3/4 inch), you can first apply fiberglass mesh tape over the gap, then cover it with mastic4.
    2. When sealing flexible duct connections, some professionals recommend using high-quality duct tape first, then sealing with mastic for added protection2.
    3. In cases where immediate temporary sealing is needed before mastic can fully cure, tape might be used as an initial layer4.

    Remember, when applying mastic:

    • Clean the surface thoroughly before application5.
    • Apply a generous amount, ensuring complete coverage of the joint or seam16.
    • Allow 24-48 hours for the mastic to fully cure3.

    In most cases, properly applied mastic alone is sufficient for sealing HVAC joints without the need for additional taping.

  • HVAC tape ratings ul-181 a-p and ul181b-fx explained

    UL-181A-P and UL181B-FX are important ratings for HVAC tapes, indicating their compliance with specific Underwriters Laboratory (UL) standards:

    1. UL-181A-P:
      • Used for seaming, sealing, and joining rigid fiberglass ductwork (duct board) and sheet metal13.
      • Made of aluminum or aluminum alloy foil with a minimum width of 2.5 inches13.
      • Features an aggressive acrylic adhesive and often includes a release liner3.
      • Designed to withstand the thermal cycles of HVAC systems3.
    2. UL181B-FX:
      • Specifically used for Class 1 flexible air ducts and connectors123.
      • Can be made of foil, film, or cloth with a maximum width of 1.88 inches3.
      • Some UL181B-FX tapes can be used as alternatives to traditional paint-on mastic3.

    Both ratings ensure that the tapes have passed rigorous testing for flame resistance, mold growth, humidity resistance, temperature performance, and other critical factors1. These certifications are crucial for code compliance and guarantee that the tape will effectively seal HVAC systems for their intended lifespan when properly installed3.

    It’s worth noting that a UL181A-P certified product is always certified to UL181B-FX as well, and may carry the designation UL181A-P/B-FX2

  • Mastic on your flexible duct

    Mastic can be brushed on flexible duct124. Mastic is a versatile air duct sealant that can be applied using various methods, including brushing, to seal joints and seams in flexible air ducts24. When applying mastic to flexible duct:

    1. Ensure the surface is clean and dry before application7.
    2. Use a brush to apply the mastic directly on the duct, not on the insulation or sleeve7.
    3. For gaps larger than 1/4 inch, use fiberglass mesh tape in combination with mastic for a more secure seal7.
    4. Allow the mastic to dry completely after application5.

    Mastic sealant is preferred over duct tape for sealing flexible ducts because it creates a more durable, flexible, and long-lasting seal that can withstand temperature changes and vibrations4. When applied correctly, mastic sealant can last up to 20 years or longer, significantly improving HVAC system efficiency and reducing maintenance requirements4.

  • When building a large ductboard return duct into the furnace, are there any rules on how the duct collar should be built

    According to North Carolina building codes, there are specific requirements for constructing duct collars when building a large ductboard supply duct into the furnace:

    1. All connections, including the duct collar, must be sealed with water-based duct mastic1. This is critical for meeting the new North Carolina Energy Conservation Code (NCECC) requirements.
    2. Tape can be used during installation, but should not be relied upon as the primary method of air sealing ductwork1. Mastic should be applied over the tape to ensure airtightness.
    3. The duct collar should be properly sized and well-sealed where it meets the air handler1. This is particularly important due to the large size of plenums, as poor connections at the air handler can lead to significant leaks.
    4. When connecting the ductboard to metal components like the furnace, a metal collar or sleeve should be used to ensure a secure and airtight connection4.
    5. The duct collar must be constructed to meet the pressure class requirements of the system4. Each size in a pressure class has minimum specifications for joints and reinforcements.
    6. Proper support for the duct collar and adjacent ductwork is required. Metal straps with a minimum width of 1 inch (25 mm) and equivalent to or heavier gauge than the duct material should be used for support8.
    7. The duct collar should be designed to allow for proper airflow and minimize pressure drop in the system4.

    Remember to consult the specific North Carolina Mechanical Code and SMACNA guidelines for detailed requirements and best practices when constructing duct collars and connections.

  • HVAC Duct leakage test

    A duct leakage tester works by pressurizing the duct system and measuring the airflow required to maintain that pressure, which indicates the amount of leakage. Here’s how the process typically works:

    1. Preparation: All supply and return registers are sealed off to isolate the duct system12.
    2. Setup: A calibrated fan (duct tester) is connected to the duct system, usually at the return side3.
    3. Pressurization: The fan pressurizes the duct system to a standard pressure of 25 Pascals, which approximates typical operating conditions1.
    4. Measurement: A manometer measures the duct pressure (typically on Channel A) and the fan pressure (on Channel B)3.
    5. Calculation: The airflow through the fan at the test pressure is measured, quantifying the duct leakage. This is typically expressed in cubic feet per minute (CFM)1.
    6. Analysis: The leakage rate is often calculated as CFM per 100 square feet of conditioned floor area. For example, a leakage of 4 CFM per 100 square feet is commonly referred to as a 4% leakage rate5.

    The test can be performed as a “total duct leakage test” or a “leakage to outside test,” depending on whether the goal is to measure all leaks or only those leaking to unconditioned spaces1. This method allows HVAC professionals to accurately assess duct system performance and identify areas needing improvement.

    Interpreting the results of a duct leakage test involves understanding the measurements and comparing them to established standards. Here’s how to interpret the results:

    1. Measurement Units: Results are typically expressed in CFM25 (Cubic Feet per Minute at 25 Pascals of pressure)35.
    2. Leakage Rate: The leakage rate is often calculated as CFM per 100 square feet of conditioned floor area. For example, 4 CFM per 100 square feet is referred to as a 4% leakage rate1.
    3. Acceptable Thresholds:
      • For rough-in tests (before drywall installation), total duct leakage should not exceed 3% or 3 CFM per 100 square feet of conditioned floor area1.
      • If the air handler is included in the rough-in test, the acceptable threshold increases to 4% or 4 CFM per 100 square feet1.
      • For post-construction tests, a leakage rate of 4% or less is generally considered acceptable8.
    4. Interpreting Results:
      • Lower CFM25 values indicate less leakage and better duct system performance.
      • Higher values suggest more significant leaks that may require attention.
    5. Compliance with Building Codes:
      • Check local building codes for specific requirements. Many jurisdictions have adopted the 2018 or 2021 International Energy Conservation Code (IECC) standards4.
    6. Energy Efficiency Programs:
      • Programs like ENERGY STAR may have their own criteria for acceptable duct leakage rates3.

    If the test results exceed the acceptable thresholds, it indicates that the duct system needs sealing or repairs to improve its efficiency and performance.

    Did somebody say building codes?

    Yes, there are specific building codes related to duct leakage. The International Energy Conservation Code (IECC) and various state-specific codes provide requirements for duct leakage testing and acceptable leakage rates. Here are some key points:

    2021 IECC Requirements

    1. All ductwork must be tested for leakage, even if it remains within the building’s thermal envelope12.
    2. For ducts outside the thermal envelope: Leakage must not exceed 4.0 CFM per 100 square feet of conditioned floor area at 25 Pascals2.
    3. For ducts inside the thermal envelope: Leakage must not exceed 8.0 CFM per 100 square feet of conditioned floor area at 25 Pascals2.

    Earlier IECC Versions (2012-2018)

    1. Total leakage limit: 4 CFM per 100 square feet of conditioned floor area at 25 Pascals4.
    2. Rough-in test limits: 4 CFM per 100 square feet with air handler installed, 3 CFM without air handler4.

    State-Specific Codes

    1. North Carolina Energy Conservation Code (2018):
      • Total duct leakage limit: 5 CFM per 100 square feet of conditioned floor area6.
      • High-efficiency option: 4 CFM per 100 square feet of conditioned floor area8.
    2. ENERGY STAR Version 3 Rev 11 criteria:
      • Rough-in: ≤ 4 CFM25 per 100 square feet or ≤ 40 CFM25, whichever is greater3.
      • Final: ≤ 8 CFM25 per 100 square feet or ≤ 80 CFM25, whichever is greater3.

    It’s important to note that building codes can vary by jurisdiction and are subject to updates. Always check with local authorities for the most current requirements in your area.

  • HVAC Pro specialized tools and measurements

    HVAC professionals use a variety of specialized tools and measurements to evaluate furnace, air conditioning, and duct systems. Here are some of the essential tools and measurements they employ:

    Airflow Measurement Tools

    1. Duct Leakage Testers: These instruments measure the airtightness of HVAC ductwork, providing accurate leakage detection and duct performance measurements12.
    2. Anemometers: Tools like the Fieldpiece STA2 In-Duct Hot Wire Anemometer measure airflow velocity in cubic feet per minute (CFM)3.
    3. Airflow Capture Hoods: These are used for measuring airflow at registers and grilles3.

    Temperature and Pressure Tools

    1. Dual Temperature Digital Thermometers: Used for conducting Delta T tests, measuring temperatures in return and supply air ducts3.
    2. Psychrometer Probes: Devices like the Fieldpiece JL3RH Job Link® System Flex Psychrometer Probes measure various parameters including relative humidity, dry bulb, wet bulb, dew point, and enthalpy3.
    3. Manometers: Used for measuring static pressure in ductwork and HVAC systems.

    Measurements and Tests

    1. Total External Static Pressure (TESP) Test: This test measures the resistance to airflow in the ductwork and HVAC components3.
    2. Delta T Test: Measures the temperature difference between return and supply air to assess system performance3.
    3. Live CFM Testing: Measures the actual airflow through the system, crucial for assessing efficiency and capacity3.
    4. Friction Loss Rate: This measurement helps determine the static pressure of air throughout the ductwork4.

    Ductwork Evaluation

    1. Duct Sizing Calculations: HVAC professionals use formulas and software to calculate proper duct sizes based on factors like square footage, friction loss rate, and CFM4.
    2. Multi-point Airflow Measurements: Following ASHRAE standards, technicians take multiple measurements across the duct cross-section to ensure accurate airflow readings5.

    By using these tools and measurements, HVAC professionals can accurately diagnose issues, optimize system performance, and ensure efficient operation of furnace, air conditioning, and duct systems.