R-22 Refrigerant Checklist

Steps an AC Repair Technician Follows to Test and Add R-22 Refrigerant

Preparation and Safety

  • Confirm the system uses R-22 by checking the manufacturer’s label or service manual.
  • Ensure you have the correct tools: R-22 manifold gauge set, R-22 refrigerant cylinder, digital scale, thermometer, and PPE (gloves, goggles, respirator).
  • Work in a well-ventilated area and follow all EPA regulations regarding R-22 handling, as it is now banned for production/import and only recycled/reclaimed R-22 is allowed15.
  • Turn off the air conditioner and set the thermostat to its lowest setting14.

Inspection and Diagnosis

  • Inspect for signs of refrigerant leaks (oil residue, hissing sounds, ice on lines) and confirm low refrigerant symptoms (warm air from vents, ice on coils)5.
  • Repair any leaks before adding refrigerant—never add refrigerant to a leaking system.

Connecting Equipment

  • Remove the service port caps from the R-22 valves on the outdoor unit14.
  • Connect the blue (low side) hose of the manifold gauge to the larger suction line port.
  • Connect the red (high side) hose to the smaller liquid line port.
  • Connect the yellow hose to the R-22 refrigerant cylinder.
  • Purge air from the hoses by briefly opening each manifold valve to release trapped air until you hear a change in sound, then close the valve127.

System Operation and Baseline Readings

  • Open the refrigerant cylinder valve with the container upright for vapor charging (common for topping off; for large charges, liquid may be added but must be metered slowly to avoid compressor damage)12.
  • Turn the AC system back on and let it run for 3–5 minutes to stabilize1.
  • Observe the initial pressure readings on the manifold gauges.

Measuring and Charging

  • Use a thermometer to measure the temperature at the suction line (about 6 inches from the service port)1.
  • Compare the suction line temperature and pressure to a pressure/temperature (P/T) chart to determine superheat (for fixed orifice systems) or subcooling (for TXV systems)12.
  • For superheat:
    • Calculate superheat: Suction line temp – Saturation temp (from low-side gauge).
    • Target superheat is typically 8–18°F; 12°F is often optimal1.
    • If superheat is too high, slowly add R-22 vapor into the low side while monitoring the readings.
    • If superheat is too low (below 7°F), the system may be overcharged.
  • For subcooling (TXV systems):
    • Calculate subcooling: Saturation temp (high-side gauge) – Liquid line temp.
    • Add refrigerant slowly if subcooling is below manufacturer specs; stop when correct subcooling is reached2.
  • Add refrigerant in small increments, allowing the system to stabilize between additions.
  • Always monitor the amount of refrigerant added using a scale for accuracy2.

Final Checks

  • Once the correct charge is achieved, let the system run for several more minutes to ensure stable operation and correct readings.
  • Check for abnormal noises, vibrations, or continued signs of leaks.
  • Close the refrigerant cylinder valve and the manifold valves.
  • Recover any refrigerant from hoses back into the system to minimize loss.
  • Disconnect the manifold hoses and replace all service port caps tightly12.

Cleanup and Documentation

  • Restore all panels and clean the work area.
  • Record the amount of R-22 added, final pressure/temperature readings, and any repairs performed for future reference.

Key Points and Differences from Modern Refrigerants

  • R-22 uses 1/4″ SAE flare fittings, while R-410A uses 5/16″ fittings.
  • R-22 can be charged as vapor or liquid (if liquid, always meter slowly into the suction side).
  • Topping off is allowed with R-22, but not with R-410A or blends.
  • R-22 is now only available as recycled or reclaimed refrigerant due to environmental regulations15.

Summary Table: R-22 Charging Steps

StepDetails
Safety/PrepConfirm R-22, PPE, tools, system off, area ventilated
InspectionLeak check, repair leaks, confirm low refrigerant symptoms
Connect GaugesBlue to suction, red to liquid, yellow to cylinder, purge hoses
System On, StabilizeAC on, run 3–5 min, observe pressures
Measure/ChargeSuperheat (fixed orifice) or subcooling (TXV), add refrigerant as needed
Final ChecksConfirm readings, system stable, no leaks, close valves
Disconnect/CleanupRecover refrigerant from hoses, remove gauges, replace caps
DocumentationRecord refrigerant added, readings, repairs